What California’s Title 24 2013 Energy Efficiency Standards Mean for Your Data Center

Posted on April 18, 2014 by Gento

California Title 24 2013 Energy Efficiency StandardsCalifornia’s Title 24 2013 energy efficiency standards will go into effect on July, 1 2014. Prior to 2013 California data centers were considered exempt from Title 24, but that’s no longer the case as most data centers will now require:

  • Economizers in small computer rooms in buildings that have economizers
  • Prohibiting reheat in computer rooms
  • Prohibiting non-adiabatic humidification in computer rooms
  • Limiting power of fan systems serving computer rooms to 27 watts/kBtuh of net sensible cooling capacity
  • Variable speed controls on all chilled water fan systems and all direct expansion (DX) systems over 5 tons serving computer rooms.
  • Containment in large, high density data centers with air-cooled computers

(Note: There are a couple of economizer exemptions you can view here)

The greatest benefit the new standards provide come in energy savings.  According to a study conducted by the California Statewide Utility Codes and Standards Program, a prototypical building that measures 20,000 sq ft and whose design IT load is 100 W per sq ft will save $520 per square foot, per year by meeting the new requirements. This amounts to $10,500,000 total yearly energy savings. 

Other significant non-energy related benefits derived from the new law will include: better computer performance as a result reduced hot spots, less fan noise due to variable speeds, improved comfort for workers since there’s no need to overcool, and backup cooling capacity from economizers should CRAH or CRAC units fail. 

However, there are potential drawbacks to the new requirements as well.  In the event of a CRAC failure, airflow containment creates a shorter window during which to get the unit up and running again before exceeding safe operating temperatures (this is true even with economizers – which will be dependent on California temperatures within a range of 64.4°F to 80.6°F – serving as backup cooling systems). 

Additionally, using economizers introduces outside air which may inadvertently admit gaseous contaminates like dust and pollen, and/or introduce higher humidity air that can lead to condensation.  Nonetheless, the new mandates are a positive step toward creating energy efficiency guidelines that may eventually have far reaching implications for data centers nationwide.

In fact improved data center environment monitoring will allow facility managers to overcome any potential drawbacks and meet requirements. In order to meet requirements for having variable speed fan speed systems and limiting power of fan systems, data centers will have to employ temperature sensors to cold aisle containments that can feed back to a BMS or DCIM software solution, that autonomously starts fans at predetermined speeds, as and when needed.

Better data center monitoring will also negate potential drawbacks. Airflow sensors can monitor flow rates of cooling and hot air return to ensure cooling and containment systems are functioning optimally. While humidity sensors can help data centers to maintain proper humidity levels, especially when drawing external air through a system of economizers.

California data centers may also wish to build upon energy savings achieved through the new energy code by implementing a DCIM monitoring solution that, in addition to collecting environment data and alerting data center managers to potential issues, can also lead to efficient IT device utilization, and intelligent power distribution.

Other Blog Posts

AI 時代下的新雲(Neocloud) 基礎架構解析
Posted on June 1, 2026
突破冷通道封閉的限制:先進感測技術如何改變資料中心冷卻
Posted on June 1, 2026
Universal Input:為資料中心帶來無縫即插即用的靈活性
Posted on March 1, 2026
智慧型 PDU:AI 資料中心電力管理的關鍵核心
Posted on December 17, 2025
遠端醫療掃描,如何優化營運並提升病患滿意度
Posted on November 24, 2025

View all Blog Posts

訂閱

近期活動

Japan Cloud & Datacenter Convention 2025
06 Jun 2025  •  Tokyo, Japan
Interop Tokyo 2025
11 Jun - 13 Jun 2025  •  Chiba, Japan
Suntelephone ICT Business Solution 2025 (Sendai)
17 Jun 2025  •  Sendai, Japan
Suntelephone ICT Business Solution 2025 (Kanazawa)
25 Jun 2025  •  Kanazawa, Japan
Suntelephone ICT Business Solution 2025 (Takamatsu)
04 Jul 2025  •  Takamatsu, Japan

View all Events

Raritan最新新聞

Legrand 推出新一代 KVM 平台,協助關鍵系統在數分鐘內恢復上線
Posted on October 22, 2026
—ISO27001 認證為 Legrand 羅格朗品牌(包括 Raritan®、Server Technology® 和 Starline® 品牌)經過徹底測試的數據、電源和控制設備的安全性提供了保證。
Posted on July 1, 2024
Legrand 使用兩大創新智慧型機架 PDU 重新活化資料中心產業
Posted on May 1, 2023
Exclusive interview丨How does Huizhou upgrade its manufacturing industry?
Posted on December 2, 2021
Raritan 發表 MasterConsole® 數位雙電腦切換器
Posted on February 18, 2021

View all news