What California’s Title 24 2013 Energy Efficiency Standards Mean for Your Data Center

Posted on April 18, 2014 by Gento

California Title 24 2013 Energy Efficiency StandardsCalifornia’s Title 24 2013 energy efficiency standards will go into effect on July, 1 2014. Prior to 2013 California data centers were considered exempt from Title 24, but that’s no longer the case as most data centers will now require:

  • Economizers in small computer rooms in buildings that have economizers
  • Prohibiting reheat in computer rooms
  • Prohibiting non-adiabatic humidification in computer rooms
  • Limiting power of fan systems serving computer rooms to 27 watts/kBtuh of net sensible cooling capacity
  • Variable speed controls on all chilled water fan systems and all direct expansion (DX) systems over 5 tons serving computer rooms.
  • Containment in large, high density data centers with air-cooled computers

(Note: There are a couple of economizer exemptions you can view here)

The greatest benefit the new standards provide come in energy savings.  According to a study conducted by the California Statewide Utility Codes and Standards Program, a prototypical building that measures 20,000 sq ft and whose design IT load is 100 W per sq ft will save $520 per square foot, per year by meeting the new requirements. This amounts to $10,500,000 total yearly energy savings. 

Other significant non-energy related benefits derived from the new law will include: better computer performance as a result reduced hot spots, less fan noise due to variable speeds, improved comfort for workers since there’s no need to overcool, and backup cooling capacity from economizers should CRAH or CRAC units fail. 

However, there are potential drawbacks to the new requirements as well.  In the event of a CRAC failure, airflow containment creates a shorter window during which to get the unit up and running again before exceeding safe operating temperatures (this is true even with economizers – which will be dependent on California temperatures within a range of 64.4°F to 80.6°F – serving as backup cooling systems). 

Additionally, using economizers introduces outside air which may inadvertently admit gaseous contaminates like dust and pollen, and/or introduce higher humidity air that can lead to condensation.  Nonetheless, the new mandates are a positive step toward creating energy efficiency guidelines that may eventually have far reaching implications for data centers nationwide.

In fact improved data center environment monitoring will allow facility managers to overcome any potential drawbacks and meet requirements. In order to meet requirements for having variable speed fan speed systems and limiting power of fan systems, data centers will have to employ temperature sensors to cold aisle containments that can feed back to a BMS or DCIM software solution, that autonomously starts fans at predetermined speeds, as and when needed.

Better data center monitoring will also negate potential drawbacks. Airflow sensors can monitor flow rates of cooling and hot air return to ensure cooling and containment systems are functioning optimally. While humidity sensors can help data centers to maintain proper humidity levels, especially when drawing external air through a system of economizers.

California data centers may also wish to build upon energy savings achieved through the new energy code by implementing a DCIM monitoring solution that, in addition to collecting environment data and alerting data center managers to potential issues, can also lead to efficient IT device utilization, and intelligent power distribution.

Other Blog Posts

從資料中心失效對企業帶來的骨牌效應──探討感測器的重要性
Posted on November 5, 2023
更高規格的電源要求加速AI市場成長與Raritan PDU的採用
Posted on October 11, 2023
資料中心服務中斷次數減少,但停機的代價仍舊可觀
Posted on September 20, 2023
意見調查:資料中心面臨能源使用與人力短缺困境
Posted on September 20, 2023
Raritan安全切換器:相容於Secure NIAP 4.0的桌上型KVM
Posted on September 20, 2023

View all Blog Posts

訂閱

近期活動

New Zealand Cloud & Datacenter Convention 2022
3 November 2022, 9am – 4pm  •  Grand Millennium Hotel, Auckland, New Zealand
Data Centre World Singapore
12th – 13th Oct 2022
Korea Cloud & Datacenter Convention 2022
6th Oct 2022
Philippines Cloud & Datacenter Convention 2022
4th Aug 2022
JANOG50 Meeting Hokkaido
3th – 15th July 2022

View all Events

Raritan最新新聞

Legrand 使用兩大創新智慧型機架 PDU 重新活化資料中心產業
Posted on May 1, 2023
Exclusive interview丨How does Huizhou upgrade its manufacturing industry?
Posted on December 2, 2021
Raritan 發表 MasterConsole® 數位雙電腦切換器
Posted on February 18, 2021
Legrand Data, Power and Control Division Announced as Finalist in Six Categories at DCS Awards 2020
Posted on November 9, 2020
Raritan 新款智慧機櫃控制器 (SRC) 可智慧管理資料中心與關鍵任務設施的環境與安全性資訊
Posted on November 9, 2020

View all news