Keep it Safe: Overload Protection at the Rack

Posted on September 22, 2021 by Gento

This article from Raritan provides an overview of overload protection standards for rackmount PDUs.   

Lost in most discussions about rackmount PDUs and intelligent PDUs is a simple premise: their job is to keep you and your equipment safe. Newly certified ITE PDUs of any type and with more than 20 amps are required to use overcurrent protection that meets branch circuit protection requirements in accordance with the National Electrical Code, ANSI/NFPA 70. In effect, this means these products are required to have branch circuit breakers listed under UL 489, “Standard for Molded-Case Circuit Breakers, Molded-Case Switches and Circuit Breaker Enclosures,” or fuses listed for branch circuit protection, such as those listed under UL 248-5, “Low-Voltage Fuses – Part 5: Class G Fuses.” 

Using the Right Circuit Breaker Means Avoiding Short-Circuit Disasters 

In addition to UL Standard 489, Underwriters Laboratories also publishes UL Standard 1077, which is the “Standard for Supplementary Protectors for Use in Electrical Equipment.” Devices certified to this standard are considered “Supplementary Protectors” and are called “Recognized” components, not “Listed” devices (as UL 489 breakers are). UL Listed Circuit Breakers meet more stringent requirements for branch circuit protection than Supplementary Protectors with UL Recognition. UL 489 requires the breaker to be functional after being subjected to a short-circuit test. UL 1077 and the IEC standard EN 60934 allow for breakers to clear a short-circuit condition but become safely destroyed in the process. 

Circuit breakers are used in a variety of ways: 

  • They are mounted in panel boards (also referred to as building PDUs) and rackmount PDUs to protect branch-circuit wiring. 
  • They are also built into equipment to protect components and systems. Interrupting a short circuit—current flow limited only by the resistance of wiring—is a severe test of a circuit breaker. 
  • If the interrupting capacity of the breaker is not adequate, the device could literally explode. 

While that last bullet sounds a little dramatic, it is a friendly reminder that the amount of energy being harnessed in the electrical systems of most data centers, even at the rack or individual circuit level, is significant. Keep in mind UL 489 breakers can interrupt short circuits of 5,000 amps or more and UL 1077 breakers can interrupt fault currents of 1,000 amps. 

Overload Protection and Rack Mount PDUs 

If you would like more information on the topic of data center overload protection, check out our White Paper “Data Center Power Overload Protection: Circuit Breakers and Branch Circuit Protection for Data Centers”. 

Contact us here at Raritan to learn more about how our rackmount PDUs can support your power safety needs. 

Other Blog Posts

AI 時代下的新雲(Neocloud) 基礎架構解析
Posted on June 1, 2026
突破冷通道封閉的限制:先進感測技術如何改變資料中心冷卻
Posted on June 1, 2026
Universal Input:為資料中心帶來無縫即插即用的靈活性
Posted on March 1, 2026
智慧型 PDU:AI 資料中心電力管理的關鍵核心
Posted on December 17, 2025
遠端醫療掃描,如何優化營運並提升病患滿意度
Posted on November 24, 2025

View all Blog Posts

訂閱

近期活動

Japan Cloud & Datacenter Convention 2025
06 Jun 2025  •  Tokyo, Japan
Interop Tokyo 2025
11 Jun - 13 Jun 2025  •  Chiba, Japan
Suntelephone ICT Business Solution 2025 (Sendai)
17 Jun 2025  •  Sendai, Japan
Suntelephone ICT Business Solution 2025 (Kanazawa)
25 Jun 2025  •  Kanazawa, Japan
Suntelephone ICT Business Solution 2025 (Takamatsu)
04 Jul 2025  •  Takamatsu, Japan

View all Events

Raritan最新新聞

Legrand 推出新一代 KVM 平台,協助關鍵系統在數分鐘內恢復上線
Posted on October 22, 2026
—ISO27001 認證為 Legrand 羅格朗品牌(包括 Raritan®、Server Technology® 和 Starline® 品牌)經過徹底測試的數據、電源和控制設備的安全性提供了保證。
Posted on July 1, 2024
Legrand 使用兩大創新智慧型機架 PDU 重新活化資料中心產業
Posted on May 1, 2023
Exclusive interview丨How does Huizhou upgrade its manufacturing industry?
Posted on December 2, 2021
Raritan 發表 MasterConsole® 數位雙電腦切換器
Posted on February 18, 2021

View all news