Three Places Rack PDUs Capture Power Data From and Why You Should Care

Posted on July 10, 2014 by Gento

Power Distribution Unit PDU Detail

One aspect of intelligent rack PDUs that’s often poorly understood is where the devices are actually capable of capturing power data from;  And more importantly, the distinct advantages to monitoring the power drawn from IT devices, PDU breakers, and branch circuits that can help you to develop energy efficiency standards and lower the risk of unplanned downtime.  So when monitoring power via rack PDU, consider the advantages of monitoring at the outlet-level, PDU breaker, and PDU branch circuit. 

1. Why monitor at the outlet?

  • Monitoring at the outlet allows for trending load to the IT device. By trending at the IT device you can use this data for capacity planning.  For instance, you will know what a new IT device, of the same type, can expect to draw.
  • If you monitor at the outlet, you can set thresholds below the breaker trip threshold, such that, if a single power supply is approaching the outlet threshold, you can remediate it by powering off the outlet automatically or manually.  This may eliminate a cascading failure.

2. Why monitor at the PDU breaker?

  • Monitoring at the breaker allows the PDU to know when a breaker trips.  And not just when a breaker trips, but which breaker so that you’re able to quickly reset.

3. Why monitor at the branch circuit of the PDU?  

  • When you have a 3-phase system, you can more easily monitor for balancing across the branches.
  • Keep in mind that branch circuit load is different than line load because of the 3-phase line pairs.  Line load rating is usually going to much higher than branch load rating.  Each branch will typically have a 20A breaker, where each phase of a 60A 3PH circuit will have a 48A rating.  So, you need to know, not only the load of the phases, but also each branch.
  • In high power PDUs (40A or higher), there are 6 branches (6 breakers), 2 per phase.  In this case you can be balanced among the phases but not balanced along the branches.   So, monitoring at the branch allows you to check for balance among the branches as well as the phases.
  • Besides knowing about balancing, monitoring branches will also allow you to calculate whether a failover can be accommodated by the other branches.
  • Monitoring branch circuits allows you to set thresholds to prevent breakers from tripping.

Learn more about Raritan’s data center power management solutions or request a custom demo with a Raritan expert today! 

Other Blog Posts

AI 時代下的新雲(Neocloud) 基礎架構解析
Posted on June 1, 2026
突破冷通道封閉的限制:先進感測技術如何改變資料中心冷卻
Posted on June 1, 2026
Universal Input:為資料中心帶來無縫即插即用的靈活性
Posted on March 1, 2026
智慧型 PDU:AI 資料中心電力管理的關鍵核心
Posted on December 17, 2025
遠端醫療掃描,如何優化營運並提升病患滿意度
Posted on November 24, 2025

View all Blog Posts

訂閱

近期活動

Japan Cloud & Datacenter Convention 2025
06 Jun 2025  •  Tokyo, Japan
Interop Tokyo 2025
11 Jun - 13 Jun 2025  •  Chiba, Japan
Suntelephone ICT Business Solution 2025 (Sendai)
17 Jun 2025  •  Sendai, Japan
Suntelephone ICT Business Solution 2025 (Kanazawa)
25 Jun 2025  •  Kanazawa, Japan
Suntelephone ICT Business Solution 2025 (Takamatsu)
04 Jul 2025  •  Takamatsu, Japan

View all Events

Raritan最新新聞

Legrand 推出新一代 KVM 平台,協助關鍵系統在數分鐘內恢復上線
Posted on October 22, 2026
—ISO27001 認證為 Legrand 羅格朗品牌(包括 Raritan®、Server Technology® 和 Starline® 品牌)經過徹底測試的數據、電源和控制設備的安全性提供了保證。
Posted on July 1, 2024
Legrand 使用兩大創新智慧型機架 PDU 重新活化資料中心產業
Posted on May 1, 2023
Exclusive interview丨How does Huizhou upgrade its manufacturing industry?
Posted on December 2, 2021
Raritan 發表 MasterConsole® 數位雙電腦切換器
Posted on February 18, 2021

View all news