The Raritan Blog

Flexible 400V Power Distribution

Greg More
August 30, 2010

Today’s high power demands, increasing power costs and constantly changing equipment require data center and facilities managers to look for power solutions that can deliver a lot of power but are flexible. A typical data center has both medium density (5-10 kW/rack) and high density (15-30 kW/rack) equipment racks. For example, some racks may have 2U/4U application and database servers, others may have 1U Web servers, still, others may support blade servers, storage networks, or high density networking fabric.

The power requirements for this variety of equipment can range from single phase to three phase, rack power (kW) may be anywhere from 5 kW to 30 kW per rack, and there could be dozens of different physical receptacles. The key is to efficiently utilize the available power capacity and to maintain uptime to the greatest extent possible while changes are made. The traditional approach uses pedestals at several locations in the data center with under-floor conduits or whips from the pedestal to racks. All the cable under that raised floor can impede airflow and cooling. The fixed feeds lead to decreased flexibility and challenging serviceability. In fact, it is not uncommon for some cables to be abandoned in place.

Another approach worth considering is 400V three-phase power provided by overhead track busways with plug in modules which in turn feed intelligent rack PDUs. This deployment frees up more useable floor space than the pedestal approach. It also reduces the cable clutter under the raised floor for better air flow and cooling.

 

Both single and three-phase loads can be supplied from one busway so varying power densities can be fed with the same infrastructure. Some systems allow data center staff to add and remove circuits without de-energizing loads. This makes it easy to change voltage, current, and receptacle configurations as needs change. Power connections can be added and changed when needed which defers costs.

Running 400V from the busway directly to 400V rack PDUs eliminates transmission losses (480V–208V / 120V (4% loss) vs. 400V (0%)). Processors at 120V have 18% loss vs. processors at 230V (Line - Neutral at the PDU) which have a 15% loss. This deployment provides a net improvement of 7% (4% + (18%-15%)).

The rack PDU provides branch circuit overload protection at the rack and addresses the practical physical limitations to delivering multiple circuits such as for blade servers with multiple power supplies.

If an intelligent rack PDU (iPDU) is used, sophisticated energy metering, monitoring and management as well as environmental monitoring can be easily installed. This allows data center managers to monitor temperature and follow the latest ASHRAE guidelines to lower cooling costs.  The power metering allows managers to determine actual power requirements so they can do informed capacity planning. Armed with information from iPDUs and the flexibility of busway power, changes can be made as needs and layouts change. This means efficient use of available power including freeing up “stranded” power. The environmental monitoring ensures changes don’t lead to undetected hot spots.

For more detailed information about flexible 400V power distribution join Raritan September 30, 2010 at the Datacentre Dynamics show in Chicago.

Other Blog Posts

Universal Input: Delivering Seamless Plug-and-Play Flexibility in Data Centers with Universal Input
Posted on January 12, 2026
The Intelligent PDU: A Critical Component for Power Management in AI Data Centers
Posted on December 17, 2025
How Remote Medical Scanning Streamlines Operations and Improves Patient Satisfaction
Posted on November 24, 2025
Why Residual Current Monitoring Is Essential in Data Centers
Posted on November 24, 2025
Optimizing Data Center Rack Resiliency for AI Workloads
Posted on November 24, 2025

View all Blog Posts

Subscribe


Upcoming Events

CiscoLive 2026
May 31 – June 3  •  Mandalay Bay Convention Center - Las Vegas, NV
2026 OCP Global Summit
October 12 - 15  •  San Jose Convention Center - San Jose, CA
DCD Connect VA
November 3 – 4  •  Lansdown Resort - Leesburg, VA
Dell Technologies World
May 18 - 21  •  The Venetian - Las Vegas, NV

View all Events

Latest Raritan News

Greater Choice, Scalability, Speed: Why Legrand is Doubling Down on Open Compute Project Innovations
Posted on October 3, 2025
Legrand Brings Greater Flexibility to Data Center Operators with New Intelligent Rack PDU Universal Input Option
Posted on February 26, 2025
Legrand Expands Full Suite of DX2 SmartSensors, Keeping Data Centers Ahead of Rack Power and Environmental Monitoring Challenges
Posted on December 18, 2024
Legrand Wins Back-to-Back Awards for Intelligent Rack Power Distribution Innovation
Posted on May 24, 2024
Legrand Certifications and Process Controls Provide Confidence in Information Security for Network-Connected Devices in Data-Related Applications
Posted on April 1, 2024

View all news