Seven Steps to Selecting a Rack PDU for Your Data Center

Posted on September 16, 2015 by Gento

As you can imagine, a wide variety of rack power distribution unit (PDU) configurations are available based on parameters such as: number of phases, voltage, total amps, branch circuits, number of outlets, socket type, plug type, rack units consumed, and physical dimensions. Beyond the functions of the basic rack PDU, additional capabilities are available in rack PDU categories we call metered, switched, and intelligent PDUs.

Furthermore, if you cannot find an off-the-shelf rack PDU that matches your specific requirement, some vendors will assemble or even design a custom rack PDU (also called BTO/ETO: built-to-order/engineered-to-order). Here, we'll discuss seven basic steps you should follow to help you to select and deploy the appropriate rack PDUs for your data center.

New data centers and existing data centers where power needs to be deployed to the rack should follow steps 1-7 in order. Existing data centers where power is already deployed to the rack should follow the same steps in the following order: 4, 2, 1, 3, 5, 6, 7


1. Confirm the Infrastructure Voltage

  • For North America the input voltage is likely to be 120V single phase, 208V single phase, 208V three phase, or 400V three phase.

2. Establish the Rack Kilowatt Budget

  • Estimate the total power (kW, kVA) required.
  • Determine the nameplate power rating of each device and calculate a budgeted power requirement, e.g. the sum of the nameplate values x 70%.
  • Should additional power headroom be considered to accommodate future growth or accommodate different devices?

3. Determine the Circuits, Phase, and Amperage for the Rack

  • Determine the PDU input voltage including the number of phases and amperage. This will determine the rack PDU plug type.
  • For a data center where the power is already deployed to the rack, one of the best and easiest ways to determine the required PDU input is to know the receptacle into which the PDU will be plugged.

4. Find Out What Devices will be in the Rack

  • This will determine the PDU outlet type(s) and the number of outlets required.
  • What types of plugs are used on the devices in the rack, e.g. C-14 and C-20

5. Decide if Switching is Desired and What Level of Metering is Required

  • Is remote power control required in order to reboot hung servers or keep outlets off to prevent unauthorized access, ensure proper provisioning, and avoid tripped breakers?
  • Is PDU inlet-level metering sufficient, or is the additional detail of outlet-level metering desired?

6. Learn the Rack PDU Installation Options

  • Determine the form factor that best fits the racks: typical horizontal PDU form factors are 1U (1.75 in., 44 mm) and 2U (3.5 in., 88 mm) high, there are also Zero U vertical PDUs of varying lengths.
  • Find the power inlet location, i.e. where the power feed should enter the PDU. Consider how the input feed cable routes through the rack and cable bend radius.  Typical cable feed options for rack PDUs are bottom/front, bottom/end, and top/end.
  • Decide on the proper length of the PDU input power cord.
  • Consider how the device plugs will be prevented from accidentally unplugging. There are retention clips, specially designed locking outlets or special power cords.

7. Figure Out if Advanced Features are Needed

  • Will environmental monitoring be used?
  • Will the PDU be connected to the LAN via hardwire Ethernet connections, Wi- Fi, or Gigabit Ethernet? Do PDUs need to be cascaded/daisy chained together to minimize Ethernet drops?
  • Are colors desired to indicate different power feeds, e.g. A and B feeds, or different power chains?

Lastly, should you need help with any of these steps, leave your question below in the comment field or reach out to our team of Raritan power experts.  And do visit our PDU product selector to see all of the models that are readily available for you to purchase. 

Other Blog Posts

從資料中心失效對企業帶來的骨牌效應──探討感測器的重要性
Posted on November 5, 2023
更高規格的電源要求加速AI市場成長與Raritan PDU的採用
Posted on October 11, 2023
資料中心服務中斷次數減少,但停機的代價仍舊可觀
Posted on September 20, 2023
意見調查:資料中心面臨能源使用與人力短缺困境
Posted on September 20, 2023
Raritan安全切換器:相容於Secure NIAP 4.0的桌上型KVM
Posted on September 20, 2023

View all Blog Posts

訂閱

近期活動

New Zealand Cloud & Datacenter Convention 2022
3 November 2022, 9am – 4pm  •  Grand Millennium Hotel, Auckland, New Zealand
Data Centre World Singapore
12th – 13th Oct 2022
Korea Cloud & Datacenter Convention 2022
6th Oct 2022
Philippines Cloud & Datacenter Convention 2022
4th Aug 2022
JANOG50 Meeting Hokkaido
3th – 15th July 2022

View all Events

Raritan最新新聞

Legrand 使用兩大創新智慧型機架 PDU 重新活化資料中心產業
Posted on May 1, 2023
Exclusive interview丨How does Huizhou upgrade its manufacturing industry?
Posted on December 2, 2021
Raritan 發表 MasterConsole® 數位雙電腦切換器
Posted on February 18, 2021
Legrand Data, Power and Control Division Announced as Finalist in Six Categories at DCS Awards 2020
Posted on November 9, 2020
Raritan 新款智慧機櫃控制器 (SRC) 可智慧管理資料中心與關鍵任務設施的環境與安全性資訊
Posted on November 9, 2020

View all news